LZT Acrylic Rotameter
LZT-G Inline Acrylic Rotameter with Alarm Switch
LZT-G inline (piped) acrylic rotameter supplied with flow alarm switches on the tube rail - limit alarms on a DN15-DN75 threaded pipeline meter. Switch rated max DC24V/AC24V, 0.3A, IP65, 0-55°C, set point adjustable across the span; LZT-G body accuracy ±4%, choices of port and O-ring materials.
Specifications
- Model
- LZT-G Alarm Type - inline (piped) LZT-G acrylic rotameter supplied with flow alarm switch(es)
- Body
- LZT-G inline acrylic rotameter; acrylic tube with threaded end fittings; internal (ZG) or external (ZG) thread
- Alarm Switches
- One or two magnetic reed switches sliding on the tube dovetail rail; upper-limit and/or lower-limit alarm; set point adjustable anywhere across the flow span
- Alarm Logic
- At the set position the contact closes; past it towards the range end it stays closed; returning below the set point re-opens it (factory upper/lower limit diagram)
- Switch Voltage
- Max DC24V / AC24V
- Switch Current & Contacts
- Working current max 0.3A; contact constant current max DC0.1A; breaking power max 1VA; forward resistance <200 ohm; insulation resistance >10^10 ohm
- Switch Protection
- IP65 (alarm switch only)
- Switch Working Temperature
- 0 to +55°C (alarm switch)
- Hysteresis & Dimensions
- Hysteresis (on/off position difference) 4mm; switch body 45 x 20 x 45 mm
- Wiring
- Relay coil or sound-light alarm at 24VDC; PLC input wiring per the factory diagram
- Nominal Sizes
- DN15, DN20, DN25, DN40, DN50, DN75 (LZT-G series)
- Flow Ranges
- Liquid (GPM and LPM) and gas (m3/h) spans per the LZT-G table; the span is selected at order for the medium in use
- Accuracy
- ±4% of full scale
- Medium
- Liquid or gas, depending on model selection
- Wetted Material Options
- PVC, PP, ABS, brass, chrome-plated brass or stainless steel; O-ring silicone, fluoro rubber or NBR
- Pressure & Temperature
- Not stated for this alarm variant in the factory material - confirm the working pressure and medium temperature at order
- Installation Notes
- Mount away from strong magnetic fields (e.g. large motors); the medium must be free of ferromagnetic particles; keep the pipeline vibration-free to avoid false triggering
The Inline Body With Limit Alarms on the Rail
This is the LZT-G piped meter - the inline acrylic rotameter that sits directly in a DN15 to DN75 threaded line - supplied with one or two flow alarm switches mounted on the tube's dovetail rail. The switch slides along the scale, so the alarm point is set where the process needs it rather than at a fixed factory value.
It is the inline counterpart of the panel alarm meter: where the panel version suits instrument boards, this one puts the same alarm function on a pipeline. The switches can also be added to an LZT-G already in service, because they mount on the rail rather than inside the fitting.
Switch and Body Specifications
The reed switch is a dual-stable-state type rated max DC24V / AC24V and 0.3A, IP65 on the switch housing, 4mm hysteresis, 45 x 20 x 45 mm, with switch working temperature 0 to +55°C. Wiring follows the factory diagrams: a relay coil or a sound-light alarm at 24VDC, or direct PLC inputs.
The LZT-G body itself measures liquid or gas with a dual GPM / LPM scale and m3/h gas scales, at ±4% of full scale, in DN15, DN20, DN25, DN40, DN50 and DN75 with internal or external ZG threads. Port material can be PVC, PP, ABS, brass, chrome-plated brass or stainless steel, and the O-ring is available in silicone, fluoro rubber or NBR. Working pressure and medium temperature are confirmed at order for the selected configuration.
Ordering Guidance
State the pipe size (DN15 to DN75), the medium, the flow span, the alarm direction (upper, lower or both), the switch set points and the port/O-ring materials. For the same inline body without switches see the LZT-G inline acrylic rotameter page; for the panel-mounted alarm meter see the LZT rotameter with alarm switch, and for the plastic tube version the LZS alarm page.