Flow Meter Selection Guides

Flow Meter Outputs for PLCs: 4–20 mA vs Pulse vs RS485

A flow meter can read perfectly on its own display and still be unusable to the plant if its output does not match the PLC. How to settle 4–20 mA, pulse and RS485 before ordering.

LD electromagnetic flow meter and LZDH metal tube 4-20 mA transmitter, both flanged, compared side by side
A flow meter that reads perfectly on its own display can still be useless to the plant if its output does not match what the PLC expects. The instrument gets specified by pipe size and flow range, then arrives with a signal the control system cannot read without extra hardware.
This guide covers the interface question only. It answers what an OEM or integrator must settle before ordering: what does the PLC actually need to receive, and which published output type delivers it?
The LD electromagnetic meter carries the main examples because it publishes all three output types. The LZDH metal tube meter appears as a second case where the published configuration is narrower. Where a family's output options are not fully published, this guide says so rather than inferring.

Separate the quantity from the signal

Two things a control system can want from a meter are not the same:
Instantaneous flow — the current rate, in m³/h or L/min. Control loops and trend recording use this.
Accumulated volume — the running total, in m³ or litres. Billing, batch reconciliation and consumption reporting use this.
The distinction guides the interface choice. A 4–20 mA output typically represents the rate, which the PLC can integrate over time to calculate a total. A volume-pulse output supports counting fixed increments. A serial link can provide rate, total or both, but only if the meter and protocol support those values.
A request for "4–20 mA for totalising" is not necessarily wrong; it means the PLC will normally calculate the total by integrating the received flow rate. If the buyer needs the meter's own stored total, a rate signal alone does not provide that value.

4–20 mA: a continuous rate

The 4–20 mA current loop is the default analogue interface. The meter drives a current proportional to flow and the PLC reads it through an analogue input card.
Published data. The LD lists 4–20 mA among its output options, alongside frequency or pulse and RS485, on a 220 VAC or 24 VDC supply. The LZDH publishes a two-wire 4–20 mA output on DC 24 V as its only transmission option, retaining local indication — a pointer plus an LCD showing instantaneous and accumulated flow.
What the plant adds. An analogue input card and verified scaling. The PLC maps 4 mA and 20 mA to the transmitter's configured flow span, which must be confirmed for the ordered model. Incorrect scaling produces an incorrect reading, so record the actual endpoints during commissioning.
Fits. Continuous monitoring, trending and flow-control applications, with PLC-side totalisation if required. There is no serial-protocol dependency, but confirm the actual loop wiring, power arrangement and input compatibility.
Limitation. The loop does not directly transmit the meter's internal accumulated total. A PLC-derived total depends on correct scaling, sampling and treatment of data gaps.

Pulse: volume increments

A pulse output emits a discrete pulse each time a fixed volume has passed. The PLC counts pulses and multiplies by the pulse weight.
Published data. The LD lists "frequency or pulse" in its output options. The published wording does not establish whether these are selectable modes on the same hardware or separate configurations. Confirm the ordered output type, its meaning and the pulse weight or frequency scaling before wiring.
What the plant adds. A digital counting input rated for the expected pulse frequency, plus the pulse-weight value. A high-speed counter is necessary only when a standard input cannot capture the maximum rate reliably.
Fits. Counting-based totalising, batch measurement and consumption monitoring where accumulated volume is the primary value. Pulse output does not, by itself, improve the meter's underlying measurement accuracy.
Limitation. A volume-pulse output does not directly provide a continuously updated rate; the PLC must estimate it from counts over time or pulse intervals. Signal levels, cabling and counter limits must be checked to avoid missed or spurious counts.

RS485: a serial link

RS485 is a serial interface: meter and PLC exchange data frames rather than a current level or a pulse train, so one link can carry several values.
Published data. The LD lists RS485 as an output option. That is the whole of the published statement.
What it does not publish. A protocol. RS485 defines the physical layer — a differential pair, multi-drop capable — not the message format above it. Modbus RTU is the common protocol on this layer, but the page states no protocol, and assuming Modbus because the port exists is exactly the inference that produces a meter the PLC cannot address.
Consequence. An RS485 requirement must be confirmed as a protocol requirement, not a port requirement. Ask for the protocol and, where integration work is expected, the register map: which register holds rate, which holds total, what the scaling and units are, and whether values are signed.
Fits. Multi-value data exchange and multi-drop systems when the selected meter's confirmed protocol supports the required rate and total values.
Limitation. The protocol, register map, polling interval and response performance must be confirmed for time-critical applications. An RS485 port alone does not guarantee a usable integration.

What each option asks of the PLC

The meter side of the decision is small; the PLC side is where cost and risk sit.
Requirement
4–20 mA
Pulse
RS485
Carries instantaneous rate
Yes — directly
Only by deriving it from pulse interval
Only if the protocol publishes a rate register
Carries accumulated volume
Only by PLC-side integration
Yes — counted
Only if the protocol publishes a total register
PLC hardware needed
Analogue input card
Counter-capable input; high-speed if necessary
Serial port with matching electrical interface
Scaling work
4 mA / 20 mA mapped to the configured flow span
Pulse weight and maximum input rate
Register map, units, data format
Protocol dependency
None
None
Yes — must be confirmed, not assumed
Installation checks
Loop power, load and cable routing
Signal levels, pulse rate and noise
Bus topology, termination and protocol
Best fit
Control loops, trending
Totalising, batching, consumption
Multi-value, multi-drop, SCADA
LD published output set: 4–20 mA, frequency or pulse, RS485, on 220 VAC or 24 VDC. LZDH published output set: two-wire 4–20 mA on DC 24 V, with local LCD showing instantaneous and accumulated flow. Configuration boundary: the LD product pages do not state whether different outputs are available simultaneously; confirm any multi-output requirement with the factory.

Two worked cases

Case 1 — an OEM skid reporting consumption to a customer PLC. The skid builder needs a meter on a clean water line, and the customer's PLC has an analogue input. The LD lists 4–20 mA and a 24 VDC supply option; the exact configuration, wiring and configured analogue span still need confirmation. If the customer also needs daily consumption, the PLC may integrate the received rate, subject to the accuracy and data-handling requirements. A separate pulse option can be evaluated if needed, but should not be assumed available simultaneously.
Case 2 — two-wire transmission on a metal-tube line. Here the process requires a metal tube meter and the published output choices narrow. The LZDH lists two-wire 4–20 mA at 24 VDC, plus local LCD indication of instantaneous and accumulated flow; its specification does not list pulse or RS485. It does not document a transmitted internal-total value. The PLC can calculate its own total from the 4–20 mA rate, or the buyer can request a model with a confirmed digital total output if the instrument's own total is required.
That second case shows why "PLC needs a total" must be clarified: a PLC-calculated total and retrieval of the instrument's internal total are different requirements.

What this guide does not cover

The LW turbine family publishes pulse, battery-powered display and "intelligent output" versions. It does not publish which signals the intelligent output supports, and this guide does not infer one. If a PLC interface requirement is being matched to an LW, the signal type must be confirmed against the specific model.
Yuanda's separately listed M1/M2/M3 local-indication products do not publish an electrical output. Do not generalise that limitation to the entire LZ family: the LZDH is the documented 4–20 mA transmission configuration.

Frequently asked questions

Can one meter give the PLC both rate and total? On the LD, RS485 is published as an option, so both can share one link if the protocol supports them — confirm the protocol and the registers. On an analogue-only configuration the PLC gets the rate and integrates it.
Is pulse more accurate than 4–20 mA for totalising? Not inherently. Pulse counting avoids calculating volume from a sampled analogue rate, but missed pulses and incorrect pulse weights cause errors. Analogue integration depends on scaling, sampling and data continuity. Neither changes the underlying meter accuracy.
Do I need an analogue card if I use RS485? No. RS485 is serial; the PLC needs a serial port with matching electrical characteristics.
Does the published RS485 option mean Modbus RTU is supported? No protocol is specified on the LD product page. Ask for the supported protocol, interface settings and register documentation before ordering.
Can I use an LW turbine for a PLC interface? It publishes pulse, battery-powered display and intelligent output versions, but not the signals behind intelligent output. Confirm against the specific model.

RFQ checklist: what to send for a PLC interface

Item
Why it decides the output
Which quantity the PLC needs — rate, total, or both
The primary decision; everything else follows
PLC input card available — analogue, counter, serial
The cheapest option is usually what the panel already supports
Required flow range and pipe DN
Helps select the meter; confirm the configured analogue span and maximum output pulse/frequency rate separately
Maximum pulse rate the counter accepts
Decides whether a pulse output is viable at the top of the range
Serial protocol required, if RS485
The port is published; the protocol is not
Register map needed, if integration work is expected
Rate register, total register, units, scaling, sign
Power supply available at the meter
220 VAC or 24 VDC on the LD; DC 24 V on the LZDH
Cable run length and routing
Long or noisy runs change the answer between pulse and analogue
Ambient and hazardous-area requirements
Constrains enclosure and available options
Medium and its conductivity, where relevant
Electromagnetic meters need ≥ 5 µS/cm
Whether local indication is also required
Some configurations keep the display, some do not
Initial order quantity
For quotation
Estimated annual or repeat requirement
For planning — no published MOQ or lead-time policy should be assumed
Send it through Get a Quote. The meters used as examples each have a page with the published output set: LD Integrated Electromagnetic, LD Split Type Electromagnetic and LZDH Metal Tube.
For the surrounding decisions, the companion guides cover electromagnetic flow meter sizing, electromagnetic conductivity requirements and metal tube rotameter local indication vs 4–20 mA, plus integrated vs remote electromagnetic where converter placement matters.